Ripple & Noise: 240mVp-p (max) (Measured at 20MHz by using a 12” twisted pair terminated with a 0.1uf &47uf capacitor).
Voltage Tolerance: ±2.5% (Includes set up tolerance, line regulation, load regulation).
Line Regulation: ±1.0% (Line regulation is measured from low line to high line at rated load).
Load Regulation: ±2.5%.
Setup, Rise Time: 1000ms, 50ms/230VAC; 1000ms, 50ms/115VAC at full load (Length of setup time is measured at first cost start. Turning ON/OFF the power supply may lead to increase of the setup time).
Hold up Time: 20ms/230VAC type; 20ms/115VAC at full load typical.
Input Voltage: 90-264VAC, 127-370VDC (Derating may be needed under low input voltages. Check the derating curve for more details.).
Input Frequency Range: 47-63 Hz.
Power Factor: PF>0.91/230VAC typical; PF>0/95/115VAC at full load typical.
Efficiency: 91% typical.
AC Current: 1.3A/115VAC typical; 0.6A/230VAC typical.